3.3.4

Operation modes

Building Technologies
Fire Safety
The FDCIO223 input/output module features the following modes:
Normal operation
Test/inspection
Localization
Normal operation
The input/output module FDCIO223 is in intended operation. The inputs are
monitored and evaluated. The outputs can be triggered.
Test/inspection
With test mode/inspection mode, the input/output module functions according to
how the input/output and fire control panel are configured.
Instead, activation in test mode/inspection mode will merely be signaled by means
of LEDs on the input/output module.
If the input/output module FDCIO223 is operated with a control panel FS20/FS720,
no control outputs will be triggered in the event of activation in test mode/inspection
mode.
The input/output module is meant to respond quickly in test mode/inspection mode.
Consequently, the lines are operated as follows in test mode:
With detector lines, the alarm verification is deactivated
With contact inputs, the filter time is deactivated
Error messages are transmitted immediately and are not filtered.
Localization
To enable clear identification, the FDCIO223 input/output module can be set to
localization mode from the control panel.
Localization mode is signaled by the LEDs.
See also