The device supports standard Wiegand 26
/ Wiegand 34 output, so you can connect it
with most of the access control devices by
now.
DATA0
WD0
DATA1
WD1
GND
GND
RXD
TXD
GND
Access Control Panel
485+
485-
(1) Please keep the distance between the device and access control or card reader less than 90 meters
(Please use Wiegand signal extender in long distance or interference environment).
(2) To keep the stability of Wiegand signal, connect the device and the access control or card reader in
same 'GND' in any case.
8.Other Functions
(1) Manual Reset:
If the device does not work properly because of misoperation or
other
abnormality, you can use 'Reset' function to
Operation: Remove the black rubber cap, then stick the Reset
button hole with
a sharp tool (the tip diameter is less
(2) Restore Factory Settings:
You can use the tamper switch to restore factory settings, such as
device number, system password, IP address, RS485 address.etc.
The user data won't be cleared.
Operation: Press the tamper switch three times after the alarm being
triggered 30 seconds, but no more than 60 seconds.
9. Communication
There are three modes that the PC software could communicate and exchange information with the device:
RS232, RS485 and TCP/IP, and the last two modes support remote control.
(1) RS232 Mode:
Terminals definition, please refers to the right table:
7. Wiegand Input
The device has the function of Wiegand
signal
supports to connect with
an independent
card reader.
They are installed each side of the door, to control the
lock and access together.
+12V
+12V
GND
GND
DATA1
IWD1
DATA0
IWD0
RLED
RLED
GLED
GLED
BEEP
BEEP
Side View
Back View
restart it.
than 2mm).
Reset Button
Tamper Switch
Terminals
PC Serial Ports
GND
Pin5-Gnd
RXD
Pin3-Txd
TXD
Pin2-Rxd
(2) RS485 Mode:
input
. It
Please use specified RS485 wire, RS485 active
converter and bus-type wiring.
Terminals:
Terminals
485+
485-
(3) TCP/IP Mode:
About the terminals definition, please refers
to the right table.
Two ways for TCP/IP connection:
(A) Crossover cable: The device and PC
connected directly.
IP Address:192.168.1.100
Subnet Mask:255.255.255.0
10. Cautions:
(1) Power cable is connected after all the o ther wiring. If the device is
do wn the power firstly, then make some
plugging may damag e device, and it is not included in the warranty.
(2) We recommend that use the DC 3A/12V power supply. For details, please contact our technical
personnel or sales.
(3) Please read the terminals description
caused by improper operations will be out of the range of our guarantee.
(4) Keep the e xpose d par t o f wire is less than 5mm to avoid unexpected connection, and result i n m achinery damage.
(5) Please connect the GND before all the other wiring especially under the serious
to prevent the overlarge instantaneous electrostatic to damage device.
(6) If the
distance between
cable or other types of cable instead. When choosing the power supply cable, you should
consider that the transmission distance may cause voltage attenuation.
(7) Please use specified RS485 wire, RS485 active converter, and adopt bus-type wiring. If the communication
wire is longer than 100 meters, it is needed to parallel a terminal resistance on the last device of RS485 bus,
and the value is about 120 ohm.
PC Serial Ports
RS485+
RS485-
Terminals
RJ45-1
RJ45-
RJ45-3
RJ45-6
(B) Straight cable: The device and PC connected
to LAN/WAN through switch/Lanswitch.
IP Address:192.168.1.124
Subnet Mask:255.255.255.0
necessary checking. Kindly remain that any
carefully
and wiring by rule strictly. Any damage
power supply
and device
is a little long, please do not use the Internet
Warning: No operating with power on
485+
485-
485+ 485-
RS485 Bus
485+
485-
485+
485-
RS485
Converter
Wire Name
Color
TX+
White-orange
-
2
TX
Orange
RX+
White-green
RX-
Green
PC
Switch
...
operated
abnormally, please shut
hot-
electrostatic environment,