8 Configuration
In case of...
One leaving water temperature
zone
Two leaving water temperature
zones
[C‑07]=0: leaving water temperature control
Under leaving water temperature control, room frost protection is
NOT guaranteed. However, if [2‑06] is set to "1", limited frost
protection by the unit is possible:
▪ When the leaving water temperature home page is OFF and the
outdoor ambient temperature drops below 4°C, then the unit will
supply leaving water to the heat emitters to heat up the room
again, and the leaving water temperature setpoint will be lowered.
Installer reference guide
60
...then the following applies:
▪ When
the
leaving
water
temperature home page is
OFF and the outdoor ambient
temperature drops below 4°C,
then
the
unit
will
supply
leaving water to the heat
emitters to heat up the room
again, and the leaving water
temperature setpoint will be
lowered.
▪ When
the
leaving
water
temperature home page is ON,
the external room thermostat
is "Thermo OFF" and the
outdoor ambient temperature
drops below 4°C, then the unit
will supply leaving water to the
heat emitters to heat up the
room again and the leaving
water temperature setpoint will
be lowered.
▪ When
the
leaving
water
temperature home page is ON
and
the
external
room
thermostat is "Thermo ON",
then room frost protection is
guaranteed
by
the
normal
logic.
▪ When
the
leaving
water
temperature home page is
OFF, and the outdoor ambient
temperature drops below 4°C,
then
the
unit
will
supply
leaving water to the heat
emitters to heat up the room
again, and the leaving water
temperature setpoint will be
lowered.
▪ When
the
leaving
water
temperature home page is ON,
the
operation
mode
"heating", and the outdoor
ambient
temperature
drops
below 4°C, then the unit will
supply leaving water to the
heat emitters to heat up the
room again, and the leaving
water temperature setpoint will
be lowered.
▪ The selection of "cooling" or
"heating" is done via the user
interface. When the leaving
water temperature home page
is ON and the operation mode
is "cooling", then there is no
protection.
▪ When the leaving water temperature home page is ON and the
operation mode is "heating", then the unit will supply leaving water
to the heat emitters to heat up the room according to normal logic.
▪ When the leaving water temperature home page is ON and the
operation mode is "cooling", then there is no protection.
Shut-off valve
The following is only applicable in case of 2 leaving water
temperature zones. In case of 1 leaving water temperature zone,
connect the shut-off valve to the heating/cooling output.
The shut-off valve, which is in the main leaving water temperature
zone, output is configurable.
INFORMATION
During defrost operation, the shut-off valve is ALWAYS
opened.
Thermo On/OFF: the valve closes, depending on [F-0B] when there
is no heating demand from the main zone. Enable this setting to:
▪ avoid leaving water supply to the heat emitters in the main LWT
zone (through the mixing valve station) when there is request from
the additional LWT zone.
▪ activate the On/OFF pump of the mixing valve station ONLY when
there is demand. See
#
Code
[A.3.1.1.6.1] [F-0B]
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat
or external room thermostat request setting (NOT in case
of leaving water temperature setting).
Cooling: ONLY applicable for EHBX and EHVX. The shut-off valve
closes, depending on [F-0C] when the unit is running in cooling
operation mode. Enable this setting to avoid cold leaving water
through the heat emitter and the forming of condensation (e.g. under
is
floor heating loops or radiators).
#
Code
[A.3.1.1.6.2] [F-0C]
Operation range
Depending on the average outdoor temperature, the operation of the
unit in space heating or space cooling is prohibited.
Space heating OFF temp: When the averaged outdoor temperature
raises above this value, space heating is turned OFF to avoid
overheating.
#
Code
[A.3.3.1]
[4-02]
Space cooling On temp: ONLY applicable for EHBX and EHVX.
When the averaged outdoor temperature drops below this value,
space cooling is turned OFF.
"5 Application guidelines" on
page 11.
Description
The shut-off valve:
▪ 0 (No)(default): is NOT influenced by
heating or cooling demand.
▪ 1 (Yes): closes when there is NO
heating or cooling demand.
Description
The shut-off valve:
▪ 0 (No): is NOT influenced by changing
the space operation mode to cooling.
▪ 1 (Yes)(default): closes when the
space operation mode is cooling.
Description
▪ EHBH/X04+08
and
EHVH/X04+08:
14°C~35°C (default: 25°C)
▪ EHBH/X11+16
and
EHVH/X11+16:
14°C~35°C (default: 35°C)
The same setting is also used in
automatic heating/cooling changeover.
ERLQ004~008CA + EHBH/X04+08CB
Daikin Altherma – Low temperature split
4P384972-1B – 2017.04