SMA Solar Technology AG
No.
Name
232.60
EZATyp
233# Grid Start, for Off-Grid Systems Only
No.
Name
233.01
GdSocEna
233.02
GdSocTm1Str Battery state of charge
233.03
GdSocTm1Stp Battery state of charge
233.04
GdSocTm2Str Battery state of charge
233.05
GdSocTm2Stp Battery state of charge
Operating Manual
Description
Type of PV system feed-
in (expert mode, pro-
tected by
SMA Grid Guard)
Description
Enable grid request based
on battery state of charge
(expert mode)
limit for connection to the
utility grid in the standard
additional time period
in % (expert mode)
This is the valid threshold
without the additional time
period.
limit for disconnection
from the utility grid in the
standard additional time
period as % (expert
mode)
This is the valid threshold
without the additional time
period.
limit for connection to the
utility grid in the additional
time period as % (expert
mode)
limit for disconnection
from the utility grid in the
additional time period as
% (expert mode)
13 Parameters in Sunny Remote Control
Value
Explanation
Symmetric
All PV inverters are
three-phase and feed
in symmetrically.
Asymmetric
At least one PV in-
verter is single-phase
and feeds in asym-
metrically.
Value
Disable
Enable
1% to 233.03
GdSocTm1Stp
233.02
GdSocTm1Str to
95%
1% to 233.05
GdSocTm2Stp
233.04
GdSocTm2Str to
95%
SI30M-44M-60H-80H-BE-en-33
✓ ✖
Explanation
Disable
✖ ✓ Disable
Enable
–
✖ ✓ 40 %
–
✖ ✓ 80 %
‒
✖ ✓ 40 %
‒
✖ ✓ 80 %
Default
Value
–
Default
Value
135