SMA Solar Technology AG
No.
Name
232.08
GdVldTm
232.09
GdMod
232.10
GdRvPwr
232.11
GdRvTm
232.12
GdVtgMinDel Lower voltage differ-
232.13
GdVt-
gMaxDel
Operating Manual
Description
Minimum observation
time for line voltage
and frequency in the
permissible range for
connection in s (expert
mode, protected by
SMA Grid Guard)
Type of reverse feeding
into the utility grid (ex-
pert mode, protected
by SMA Grid Guard)
Maximum grid reverse
power in W (expert
mode)
Permissible time for
maximum grid reverse
power in s (expert
mode)
ence for valid grid con-
nection in V (expert
mode, protected by
SMA Grid Guard)
Upper voltage differ-
ence for valid grid con-
nection in V (expert
mode, protected by
SMA Grid Guard)
13 Parameters in Sunny Remote Control
Value
Explanation
5 s to 900 s
VDE-AR-N 4105
AS4777
220 V / 60 Hz
GridFeed
Charge and feed-
back on utility grid
If ApplSel was set to
OnGrid in the QCG,
the value GridFeed
is fixed.
If ApplSel was set to
OffGrid in the QCG,
GridFeed and
GridCharge can be
selected.
GridCharge
Charge on utility grid
0 W to 5000 W
One Sunny Island or
single-cluster system
0 W to 20000 W Multicluster system
0 s to 60 s
0.0 V to 20.0 V
VDE_AR_4105
AS4777
Off-grid
Other
220 V / 60 Hz
0.0 V to 12.0 V
VDE_AR_4105
AS4777
Off-grid
Other
220 V / 60 Hz
SI30M-44M-60H-80H-BE-en-33
Default
Value
✓ ✓ 60 s
300 s
✓ ✓
✖ ✓ 100 W
100 W
–
✖ ✓ 5 s
✓ ✓ 11.5 V
2.0 V
2.0 V
2.0 V
2.0 V
✓ ✓ 11.5 V
2.0 V
2.0 V
2.0 V
2.0 V
–