13 Parameters in Sunny Remote Control
No.
Name
232.03
GdVtgMax
232.04
GdCurNom
232.05
GdFrqNom
232.06
GdFrqMin
232.07
GdFrqMax
130
SI30M-44M-60H-80H-BE-en-33
Description
Upper maximum thresh-
old of line voltage for
voltage monitoring in V
(expert mode, pro-
tected by
SMA Grid Guard)
Maximum current from
the utility grid in A (ex-
pert mode)
Nominal grid frequency
in Hz (expert mode,
protected by SMA Grid
Guard)
Lower minimum thresh-
old of power frequency
for frequency monitor-
ing in Hz (expert mode,
protected by
SMA Grid Guard)
Upper maximum thresh-
old of power frequency
for frequency monitor-
ing in Hz (expert mode,
protected by
SMA Grid Guard)
Value
Explanation
210.01 InvVt-
230 V / 50 Hz
gNom to
264.50 V
220 V / 60 Hz
0.0 A to 50.0 A
1 inverter
SI 3.0M / 4.4M (sin-
gle-phase)
0.0 A to 50.0 A
1 inverter
SI 6.0H / 8.0H (sin-
gle-phase)
0.0 A to 100.0 A 2 inverters
SI 6.0H / 8.0H (sin-
gle-phase)
0.0 A to 150.0 A 3 inverters
SI 6.0H / 8.0H (sin-
gle-phase)
0.0 A to 50.0 A
3 inverters
SI 3.0M / 4.4M
(three-phase)
0.0 A to 50.0 A
3 inverters
SI 6.0H / 8.0H
(three-phase)
232.05
230 V / 50 Hz
GdFrqMin to
232.06
220 V / 60 Hz
GdFrqMax
40.00 Hz to
230 V / 50 Hz
232.04
GdFrqNom
220 V / 60 Hz
232.4 GdFrqNo
230 V / 50 Hz
m to 70.00 Hz
220 V / 60 Hz
SMA Solar Technology AG
Default
Value
✓ ✓ 264.50
V
242.00
V
✖ ✓ 16 A
✖ ✓ 16 A
✖ ✓ 16 A
✖ ✓ 16 A
✖ ✓ 16 A
✖ ✓ 16 A
✓ ✓ 50.00
Hz
60.00
Hz
✓ ✓ 47.50
Hz
59.30
Hz
✓ ✓ 51.50
Hz
60.50
Hz