Declaration Of Conformity - OutBack Power GS7048E Operator's Manual

Radian series inverter / charger; input / output / bypass assembly
Hide thumbs Also See for GS7048E:
Table of Contents

Advertisement

Purpose
The intent of this document is to specify that the OutBack models listed in the Scope below conform
to the following standards for grid-interactive inverter/chargers.
This document supersedes any previous declarations for these OutBack models.
Scope
OutBack models covered by this Declaration of Conformity include the following.
GS7048E
IMPORTANT:
This Declaration of Conformity covers only the Radian Series GS7048E. This
Declaration does not cover any other models.
Standard Compliance
This product is certified by ETL to the following standards:
 IEC 61000-6-1 (EMC Standard: Immunity for Residential, Commercial, and Light-Industrial Environments)
 IEC 61000-6-3 (EMC Standard: Emissions for Residential, Commercial, and Light-Industrial Environments)
 IEC 61000-3-3 (EMC Standard: Limitation of Voltage Changes, Voltage Fluctuations, and Flicker in Public
Low-Voltage Supply Systems )
 IEC 62477 (Safety Requirements for Power Electronic Converter Systems and Equipment)
 AS3100 (General Requirements for Electrical Equipment)
 AS4777 (Grid Connection of Energy Systems via Inverters)
This product is CE compliant for all applications.
Specification Compliance
This product is declared to conform to the following specifications:
This inverter/charger model has grid-interactive functions. It is tested to certain limits for acceptable
output voltage ranges, acceptable output frequency, total harmonic distortion (THD) and
anti-islanding performance when the inverter exports power to a utility source. The OutBack
inverter/charger model listed in this document is validated through compliance testing. The following
specifications refer to exporting power to a simulated utility source of less than 1% voltage total
harmonic distortion (THD).
 The THD of the root mean square (RMS) current is less than 5%.
 The output of the Radian inverter exceeds the minimum power factor of 0.85 with a typical power factor of
0.96 or better.
907-0007-01-00 Rev A

Declaration of Conformity

for Radian Series Inverter/Chargers

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GS7048E and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Gs-iob-230vac

Table of Contents