Section 10: Fieldbus Specifications
September 2013
•
Integrator (25 ms)
•
Signal Characterizer (30 ms)
Custom Function Blocks (Execution Time):
•
Control Selector (15 ms)
•
Output Selector (20 ms)
Power:
•
Two Wire Device; Fieldbus Polarity Insensitive
•
Current Draw: 18 mA (9 to 32 VDC)
•
Device Certifications: IS / FISCO
•
Maximum certified input Voltage for IS: 30V
•
Maximum certified input current for IS: 300mA
•
Maximum certified input power for IS: 1.3W
•
Internal Capacitance (Ci): 0 nF
•
Internal Inductance (Li): 0 H
10.2
Resource Block
The Resource Block parameter table is shown in Table 10-1 on the following pages. Parameters 1
through 41 are standard Fieldbus Resource Block parameters; parameters 42 through 66 support
Field Diagnostics. Parameters 67 through 92 are Emerson device specific parameters which sup-
port Common Software Download and PlantWeb Alerts.
10.3
User Transducer Block 1200
This transducer block contains the parameters and methods for operation, configuration k and cal-
ibration of the 1066pH. A table of its parameters appears in Table 10-2 on the following pages..
10.3.1
Transducer Block Modes
The User Transducer Block per ITK 6 specifications has 3 modes of operation which determines
which parameters can be written to and the status of the measured variables. These can be sum-
marized as follows:
•
Automatic Mode
–
–
–
54
All parameters related to configuration of the local display can be written to.
The Primary Value can be simulated
Status of measured variables: Good
1066 Transmitter Instruction Manual
LIQ_MAN_1066-P-FF
Fieldbus Specifications