Toshiba PDP003Z Manual page 10

Profibus-dp option function
Hide thumbs Also See for PDP003Z:
Table of Contents

Advertisement

3.3.1.
Tolerance Range (ZSW Bit 8)
If the setpoint is changed:
1. ZSW Bit 8 is set 0
2. Calculate the tolerance.
3. Start the timer which will time-out based on parameter Tmax.
PDP003Z checks that the timer (Tmax) has not timed-out and if the actual value is within
the tolerance. If both conditions are fulfilled ZSW Bit 8 is set 1 and the timer is stopped.
The figure shows ZSW 8 when Tolerance (
Tolerance
= 0x4000 * 50%
HIW
15s
Tmax
= 3s
ZSW Bit 8
setpoint
actual value
20s
25s
Tmax
- 9 -
) is 50% and Tmax (
c157
30s
Tmax
E6581738
) is 3s.
c151
HIW = 0x4000
HIW = 0x3000
HIW = 0x2000
HIW = 0x1000
HIW = 0x0000
Time