4.1. How to use

The purposes are adjustment by real time command transmission, and the monitor of an
operation state by using cyclic communication of PROFIBUS.
Example 1: Command transmitting
When you want to set "0xC400" to parameter fa06, set "1 (FA06)" to parameter
c001
And Since 0 and 1 byte of the PZD1 supports the parameter
here, "0xC400" will be set as
VF-MB1
Parameter
1 (FA06)
c001
c002
c003
...
"C400" is set as parameter fa06
Example 2: State monitoring
When you want to monitor the output current, set "3 (FD03)" to parameter
The value of the parameter fd03 specified as 0 and1 byte of the PZD1 with the
parameter
VF-MB1
Parameter
c021
3 (FD03)
c022
c023
...
The value of a parameter fd03 is outputted.
.
Value
...
...
...
is inputted.
c021
Value
...
...
...
.
fa06
PDP003Z
PDP003Z
- 18 -
E6581738
, if "0xC400" is set up
c001
PROFIBUS Master
PZD1
PZD2
C4
00
...
...
...
.
c021
PROFIBUS Master
PZD1
PZD2
xx
xx
...
...
...
PZD3
...
PZD3
...