ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60 (Continued)
Air Handler Models
Heater Models
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
48D
6HK(1,2)6501306
6HK(1,2)6501506
6HK(1,2)6501806
6HK(1,2)6502006
6HK(1,2)6502506
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
60C
6HK(1,2)6501306
6HK(1,2)6501506
6HK(1,2)6501806
6HK(1,2)6502006
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
60D
6HK(1,2)6501306
6HK(1,2)6501506
6HK(1,2)6501806
6HK(1,2)6502006
6HK(1,2)6502506
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the
National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
8
Heater
1,2
Amps
Min. Circuit Ampacity
@240V
208V
10
19.9
20
30.8
32
44.0
40
52.4
52
65.6
60
74.0
72
87.3
80
95.7
100
117.3
10
19.9
20
30.8
32
44.0
40
52.4
52
65.6
60
74.0
72
87.3
80
95.7
10
19.9
20
30.8
32
44.0
40
52.4
52
65.6
60
74.0
72
87.3
80
95.7
100
117.3
Field Wiring
230V
208V
20.7
25
32.7
35
47.3
45
56.6
60
71.3
70
80.5
80
95.2
90
104.4
100
128.3
125
20.7
25
32.7
35
47.3
45
56.6
60
71.3
70
80.5
80
95.2
90
104.4
100
20.7
25
32.7
35
47.3
45
56.6
60
71.3
70
80.5
80
95.2
90
104.4
100
128.3
125
Johnson Controls Unitary Products
3
MOP.
230V
25
35
50
60
80
90
100
110
150
25
35
50
60
80
90
100
110
25
35
50
60
80
90
100
110
150