11-2. Back up/import settings data

The settings data that have been made from the Web Browser for Initial Settings can be exported to an HDD as a
backup.
The exported data can be imported back to the AE-200/AE-50/EW-50 to restore the previous settings after
AE-200/AE-50/EW-50 replacement.
Click [Utility] in the menu bar, and then click [Back up/import settings data] to access the Back up/import settings
data screen.
Note: Back up/import settings data function is accessible only if logged in as a maintenance user.
Data import source
The path to the file to be
imported will appear.
11-2-1. Backing up settings data
(1) To back up the data, click [Back up settings data]. The settings data will be created and the Window's
standard file download dialog will appear.
Note: It will take a few minutes to create the settings data.
Note: The name of the settings data will be "SettingData.dat".
WT07417X01
46
Back up settings data
Click to back up the EW-50
settings data.
Browse...
Click to browse for a file
that contains the data to be
imported.
Import settings data
Click to import the file
specified in the "Data import
source" field to the EW-50.