Installation

Do not instal ICAD before welding.
This apply for electrical as well as for
mechanical installation.
Please observe that ICAD when
connected to 24 V d.c., will send
out acoustic noise at stand still. This
has no influence on the function/
operation of the ICAD.

Use

ICAD 600A, ICAD 600A-TS and ICAD 1200A
can be used together with the following
Danfoss valves (fig. 1, 5a and 5b).
ICAD 600A
ICAD 600A-TS
ICM 20
ICMTS 20
ICM 25
ICM 32

Electrical data

Supply voltage is galvanically isolated from
in-/output.
Supply voltage
24 V d.c., +10% / -15%
Load ICAD 600A, ICAD 600A-TS: 1.2 A
ICAD 1200A: 2.0 A
Fail safe supply
Min. 19 V d.c.
Load ICAD 600A, ICAD 600A-TS: 1.2 A
ICAD 1200A: 2.0 A
Anolog Input - Current or Voltage
Current
0/4 - 20 mA
Load: 200 W
Voltage
0/2 - 10 V d.c.
Load: 10 kW
Analog Output
0/4 - 20 mA
Load: ≤ 250 W
Digital Input - Digital ON/OFF input by means
of voltfree contact (Signal/Telecom relays with
gold-plated contacts recommended) – Voltage
input used
ON: Contact impedance < 50 W)
OFF: Contact impedance > 100 kW
Digital Output - 3 pcs. NPN transistor output
External supply: 5 - 24 V d.c. (same supply as
for ICAD can be used, but
please note that the
galvanically isolated system
will then be spoiled).
50 W
Output load:
Load:
Max. 50 mA
Temperature range (ambient)
–30°C/+50°C (–22°F/122°F)
Enclosure
IP 67 (~NEMA 6)
Electrical connection
Connection to ICAD is done via M12
connectors. ICAD has two M12 male
connectors build-in:
© Danfoss A/S (RC-MDP/MWA), 2014-10
Power supply: 4 poled M12 male connector
Control signals: 8 poled M12 male connector
If ICAD is delivered with cables (1.5 m. (60
in.)) M12 female connectors: (Cable set with
M12 female connectors in other lengths are
available)
Power Supply cable with 4 poled M12
female connector
3 x 0.34 mm
I: Black
II: White (+) 24 V d.c.
III: Brown (–) 24 V d.c.
Control cable with 8 poled M12
female connector
7 x 0.25 mm
ICAD 1200A
A: Black
ICM 40
ICM 50
B: Brown (–) Digital output.
ICM 65
C: Red
ICM 100
ICM 125
D: Orange (–) GND - Ground.
ICM 150
E: Yellow (+) Analog input
F: Green (+) Analog input 0/2-10 V /
G: Blue
*) If Neutral zone / 3 point control is
selected (parameter i02 = 3) then
E and G is used as DI2 - Digital
ON/OFF input. Se fig. 9.

Electrical installation

General procedure for ICAD 600A/ICAD
600A-TS/1200A installed on all ICM valves.
All necessary electrical connections to be
made. Analog or digital operation of ICM
valve.
Fig. 6
Analog operation - 7 wired cable (A-G)
Modulation control. ICM valve to be
controlled from Danfoss electronics, type
EKC/EKE (fig. 7), or third party electronics
(like e.g. PLC).
Connect analog input signals. Currrent
(mA) or Voltage (V). See Parameter list
for configuration of analog input signals.
Yellow (+) and Orange (GND) are used for
current (mA) input.
or
Green (+) and Orange (GND) are used for
Voltage (V) input.
Blue (+) and Orange (GND) are used
for current (mA) output (optional, not
mandatory).
Fig. 6
Digital operation - 7 wired cable (A-G)
ON/OFF ICM solenoid valve operation.
ICM valve to be controlled by means of a
digital voltfree contact.
Connect digital input signals (fig. 8).
See Parameter list for configuration of
digital input signals.
Green (+) and Orange (GND) are
connected to a voltfree contact.
Digital output signals are optional, not
mandatory.
Black (–) and Orange (GND) are
connected to auxiliary relay for Common
Alarm.
DKRCI.PI.HV0.K2.02 / 520H8962
(3 x ~22 AWG) (fig. 6)
2
(+) 19 - 24 V d.c. fail safe
supply (optional).
(7 x ~24 AWG) (fig. 7)
2
(–) Digital output.
Common Alarm.
ICM fully open.
(–) Digital output.
ICM fully closed.
0/4-20 mA. *)
DI1 - Digital ON/OFF
input.
(+) Analog output
0/4-20 mA. *)
Brown (–) and Orange (GND) are
connected to an auxiliary relay indicating
ICM fully open.
Red (–) and Orange (GND) are connected
to an auxiliary relay indicating ICM fully
closed.
Supply voltage - 3 wired cable (I, II, III)
ICAD must be connected to a normal
24 V d.c. supply. As an option, a fail safe
supply is possible by means of a battery or
UPS (Uninterruptible Power Supply). When
voltage is applied as described below,
ICAD is ready to be configurated. See
Parameter list.
ICAD configuration can be done
independently whether the ICAD is
installed on the ICM valve or not.
See Mechanical installation.
Connect the White (+) and Brown (–) to a
24 V d.c. supply voltage (fig. 6).
Fail safe supply as an option (not
mandatory).
Connect the Black (+) and Brown (–) to a
fail safe supply.
Mechanical installation
General procedure for ICAD 600A/ICAD
600A-TS/1200A installed on all ICM valves
(fig. 3).
Check that the three socket set screws are
fully unscrewed counter clockwise with a
2.5 mm Hexagon key.
Mount ICAD by slowly lowering it on top
of the ICM valve.
The magnet coupling will drag the ICM
and ICAD together and in position.
Push ICAD in place.
Fasten ICM and ICAD with the three socket
set screws using a 2.5 mm Hexagon key.
Special moisture seal is damaged if
screws are removed (fig. 3, pos. A)
Neutral zone / 3 point control (fig. 9)
¡02 = 3
When ¡02 = 3 the speed given by ¡04
(opening) and i14 (closing) are active
When ¡02 = 3 the factory setting of ¡04
(opening) and ¡14 (closing) are both set to 10.
¡13 (Inverse operation) is active
¡16 = 1 (Encoder operation enable) is active.
¡13 = 0 (Direct operation)
DI1 = DI2 = OFF
ICAD/ICM maintain current position
DI1 = DI2 = ON
ICAD/ICM maintain current position
DI1 = ON, DI2 = OFF
ICAD increase opening degree
DI1 = OFF, DI2 = ON
ICAD decrease opening degree
¡13 = 1 (Inverse operation)
DI1 = DI2 = OFF
ICAD maintain current position
DI1 = DI2=ON
ICAD maintain current position
DI1 = ON, DI2 = OFF
ICAD decrease opening degree
DI1 = OFF, DI2 = ON
ICAD increase opening degree
3