Installation Guide
ICAD 600A/ICAD 1200A
Quick Start Guide
Grease
© Danfoss | DCS (ms) | 2020.01
1
Note!
Cross tighten all
3 screws to ensure
equal tightening.
Max 3 Nm torque.
3
Prefabricated ICAD cable
length Code number
Voltage ICAD terminal
(600A/1200A) [V DC]
* Do not measure inside the ICAD itself
Terminal box -
not supplied
by Danfoss
Ref.
Colour
A
Black
–
B
Brown
–
C
Red
–
D
Orange
–
E
Yellow
+
F
Green
+
G
Blue
+
I
Black
+
II
White
+
III
Brown
–
* Uninterruptable Power Supply
Please observe cable voltage drop
Distance between the applied DC transformer
and the ICAD terminal box may cause
a voltage drop. Cross section of cables and
size of DC transformer must be calculated
so that the voltage at all time at the ICAD
terminal box*, both during standstill and
24 Volt DC
during operation of ICAD, is within this range:
ONLY
1.5 m
027H0426
Min.
21
Max.
Quick Start Guide
Before you
start using ICAD:
24 Volt DC
ONLY
Description
Common Alarm
ICM fully open
ICM fully closed
GND ground
0/4 – 20 mA Input
0/2 – 10 V input or digital input
for on/off control
0/4 – 20 mA Output
Fail safe supply
Battery / UPS* 19 V DC
Supply voltage
24 V DC
3 m
10 m
027H0438
027H0427
027H0435
22
23
26.4
AN213086423355en-000501 | 1
2
15 m
24