Preset Mode
4-5-1

External Output Pattern

4-5-2

Count Range for Output Control

4-5-3

Configuration of Range

Count Values for Output
Control
34
Note An interval of 2 ms min. is required between the preset count values marked
with asterisks in the above chart, otherwise no external output can be
obtained normally.
External outputs 0 to 3 are for counter 1 and external outputs 4 to 7 are for
counter 2.
Output
0/4
Turned ON when the counter starts and turned OFF at count value 0+A.
1, 2/5, 6
Turned ON at the counter preset value + B and the counter preset value
+ D and turned OFF at count values 0+C and 0+E.
3/7
Turned ON for a preset interval after the counter finishes operating.
Always turned ON if the time is set to FFFF.
Mark
A
A count value turning external outputs 0 and 4 OFF.
B, D
A count value turning external output 1 and 5 or 2
and 6 ON.
C, E
A count value turning external output 1 and 5 or 2
and 6 OFF.
T
Time to keep external outputs 3 and 7 turning ON.
Note The configuration of the range in preset mode is briefly described below to
explain the functions of the High-speed Counter Unit. In addition to the set-
tings described in this section, a variety of settings, such as operating mode,
input type, and counter reset condition settings, are required. Refer to 5-3 DM
Area Allocation in Preset Mode Mode for data area allocation in detail.
Words m+10 to m+20 are for counter 1 and words m+30 to m+40 are for
counter 2. Count values can be set within a range of 0 to 8,388,607.
Values in parentheses are for counter 2 in the following diagram.
Output pattern
Meaning
m+10 (m+30)
External output 0 (4)
OFF count value
m+11 (m+31)
External output 1 (5)
ON count value
External output 1 (5)
to
OFF count value
External output 2 (6)
ON count value
External output 2 (6)
m+18 (m+38)
OFF count value
m+19 (m+39)
Time to keep external output
m+20 (m+40)
3 (7) from turning ON
Section 4-5
Range
0 to 8,388,607
(0 to 8,388,606 for
count value A)
0 to 99.99 s or
always ON