The C200H-CT021 High-speed Counter Unit has two-axis pulse input functions. These functions are not iden-
tical with the pulse input functions of the C200H-CT001-V1 High-speed Counter Unit. Refer to the following
table.
Function
Pulse input
Voltage input: 50,000 cps
performance
Line driver input: 75,000 cps
Pulse input
With line driver input and without 5-V input
specification
Input setting
DM area
Reset mode
Number of modes set with DM: 11
Output specification
NPN or PNP (selectable)
8 points/common
8 points/two axes
Operating mode
Newly added: Simple counter mode
Canceled: Latch mode
Data transfer
Impossible to change the transfer area or num-
function
ber of transfer data blocks after the Unit is
turned ON.
Transfer area:
DM 0000 to DM 1999 for the C200H and
DM 0000 to DM 6655 for the C200HS, C200HX,
C200HG, and C200HE
IORD/IOWR
Available
instructions
External forced
Set with IR bits.
output
Not controlled with ladder programs.
Available only when external outputs are not
inhibited. Enabled with a DM command.
Sign indication
+: 0, –: F
Number of
16 sets for two counters
comparative upper
and lower limits
Number of preset
20 sets for two counters
values
Count input signal
Up and down pulses input
Input A: Down
Input B: Up
Pulse and direction input
Input A: Direction
Input B: Pulse
Set value
BCD/Hexadecimal data
range/Present
counter value
Error clear
The error clear command can be issued with the
data transfer or IOWR instruction.
Error Flag
Kept on hold while the Unit has the error.
Cleared with the error clear command.
Error code
Read repeatedly.
Unit number
0 to F
Appendix A

Comparison with C200H-CT001-V1

C200H-CT021
C200H-CT001-V1
50,000 cps
With 5-V input and without line driver input
DIP switch
Number of modes set with DIP switch: 17
NPN output only
4 points/common
8 axes/axis
Unavailable: Simple counter mode
Available: Latch mode
Impossible to change the transfer area or num-
ber of transfer data blocks after the Unit is
turned ON.
Transfer area:
DM 0000 to DM 1999 for the C200H, C200HS,
C200HX, C200HG, and C200HE
Unavailable
Set with IR bits.
Enabled with IR command. (Enable forced out-
put)
+: 0, –: 1
16 sets/counter
20 sets/counter
Up and down pulses input
Input A: Up
Input B: Down
Pulse and direction input
Input A: Pulse
Input B: Direction
BCD data only
With the error read operation.
Cleared when the error is read.
Read only once.
0 to 9