Conversion Report - GE Multilin 889 Instruction Manual

Multilin 8 series
Hide thumbs Also See for Multilin 889:
Table of Contents

Advertisement

CHAPTER 2: CONVERTING SETTINGS FILES
Note
MULTILIN 489 TO 889 RETROFIT KIT – INSTRUCTION MANUAL
8.
To select an existing 489 file, click the button beside the Initialize Settings from SR
Settings File box and navigate to the file.
9.
Click OK to complete the process. Once this step is completed, the new file, with a
complete path, is added to the 889 software environment. In addition a Conversion
Report is generated, as described in the following section.
For more information on the EnerVista 8 Series Setup software, refer to the
Multilin 889 Instruction Manual at
2.3

Conversion Report

Once the file conversion process is complete, the conversion results are summarized in a
Conversion Report. The report is found under Device Definition in the Offline pane of the
Enervista 8 Series Setup software.
The Conversion Report can be printed using the File/Print command in the EnerVista
taskbar or can be printed from the "GUI" print button.
Save a copy of the Conversion Report immediately after the conversion, to use for
future reference. All Conversion Reports are removed and become inaccessible if the
user removes or modifies the converted file from the EnerVista 8 Series Setup
Software.
Only settings converted from the original 489 setpoint file are shown in the
Conversion Report. All other settings available in the new 889 setpoint file are set to
the default value, and must be verified by the user before putting the relay into
service.
The settings file conversion process is provisioned to reduce the effort of manually
converting settings. This conversion process does not guarantee settings accuracy. Each
successfully converted setting must be reviewed before putting the relay in service.
Settings in the Conversion Report window are linked to the appropriate settings screens.
Use the Conversion report window to navigate to the corresponding 889 settings window
to review converted settings.
http://www.gegridsolutions.com
CONVERSION REPORT
5