LOADING SETPOINTS FROM A FILE

6
2.4
Loading Setpoints from a File
Once the converted settings file has been thoroughly reviewed, and the new 889 Relay
installed, the settings file can be uploaded to the 889 Relay.
An error message occurs when attempting to upload a setpoint file with a revision number
that does not match the relay firmware. If the firmware has been upgraded since saving
the setpoint file, see the 889 Instruction Manual for instructions on changing the revision
number of a setpoint file.
The following procedure illustrates how to load setpoints from a file.
1.
Start the latest version of the EnerVista 8 Series Setup software.
2.
Select the previously saved setpoints file from the File pane of the 889 software main
window.
3.
Select the Offline > Edit Settings File Properties menu item and verify that the
corresponding file is fully compatible with the hardware and firmware version of the
target relay. If the versions are not identical, see Upgrading Setpoint Files to a New
Revision for details on changing the setpoints file version.
4.
Right-click on the selected file and select the Write Settings File to Device item.
5.
Select the target relay from the list of devices shown and click Send.
If there are no incompatibilities between the target device and the settings file, the data is
transferred to the relay. An indication of the percentage completed is shown in the bottom
of the main window.