Mechanical Installation

3 Mechanical Installation

3.1 Unpacking

3.1.1 Items Supplied
Items supplied may vary according to product configu-
ration.
Make sure the items supplied and the information
on the nameplate correspond to the order confir-
mation.
Check the packaging and the frequency converter
visually for damage caused by inappropriate
handling during shipment. File any claim for
damage with the carrier. Retain damaged parts
for clarification.
VLT
R
Automation Drive
www.danfoss.com
1
T/C: FC-302PK37T2E20H1BGXXXXSXXXXA6BKC4XXXD0
2
P/N: 131X3537
S/N: 010122G430
4
0.37kW/ 0.50HP
5
IN: 3x200-240V 50/60Hz 2.2A
6
OUT: 3x0-Vin 0-590Hz 2.4A
7
o
CHASSIS/ IP20 Tamb.50 C/122 F
* 1 3 1 X 3 5 3 7 0 1 0 1 2 2 G 4 3 0 *
Listed 76X1 E134261 Ind. Contr. Eq.
CAUTION:
See manual for special condition/mains fuse
10
voir manual de conditions speclales/fusibles
WARNING:
Stored charge, wait 4 min.
`
Charge residuelle, attendez 4 min.
1
Type code
2
Ordering number
3
Serial number
4
Power rating
Input voltage, frequency, and current (at low/high
5
voltages)
Output voltage, frequency, and current (at low/high
6
voltages)
7
Enclosure size and IP protection rating
8
Maximum ambient temperature
9
Certifications
10
Discharge time (Warning)
Illustration 3.1 Product Nameplate (Example)
NOTICE
Do not remove the nameplate from the frequency
converter (loss of warranty).
MG16D402
Operating Guide
3
9
8
o
MADE IN DENMARK
`
Danfoss A/S © 02/2017 All rights reserved.
3.1.2 Storage
Ensure that the requirements for storage are fulfilled. Refer
to chapter 8.4.1 Ambient Conditions for further details.

3.2 Installation Environments

NOTICE
In environments with airborne liquids, particles, or
corrosive gases, ensure that the IP/type rating of the
equipment matches the installation environment. Failure
to meet requirements for ambient conditions can reduce
the lifetime of the frequency converter. Ensure that
requirements for air humidity, temperature, and altitude
are met.
Voltage [V] Altitude restrictions
380–500
At altitudes above 3000 m (9842 ft), contact
Danfoss regarding PELV.
525–690
At altitudes above 2000 m (6562 ft), contact
Danfoss regarding PELV.
Table 3.1 Installation at High Altitudes
For detailed ambient conditions specifications, refer to
chapter 8.4.1 Ambient Conditions.

3.3 Mounting

NOTICE
Improper mounting can result in overheating and
reduced performance.
Cooling
Ensure that top and bottom clearance for air
cooling is provided. Clearance requirement:
225 mm (9 in).
Consider derating for temperatures starting
between 45 °C (113 °F) and 50 °C (122 °F) and
elevation 1000 m (3300 ft) above sea level. See
the frequency converter design guide for detailed
information.