Moxa Technologies ioLogik E1210 Quick Installation Manual page 2

Iologik e1200 series
Hide thumbs Also See for ioLogik E1210:

Advertisement

Connecting to the Network
The ioLogik E1200 has two built-in RJ45 Ethernet ports for
connecting standard direct or cross-over Ethernet cables.
LED Indicators
Type
Color
Description
Power
Amber
System power is ON
Off
System power is OFF
Ready
Green
System is ready
Flashing
Flashes every 1 sec when the "Locate"
function is triggered
Flashing
Flashes every 0.5 sec when the firmware
is being upgraded
Flashing
An on/off period cycle: 0.5 second shows
"Safe Mode"
Off
System is not ready.
Port 1
Green
Ethernet connection enabled
Flashing
Transmitting or receiving data
Port 2
Green
Ethernet connection enabled
Flashing
Transmitting or receiving data
EXT
Green
EXT field power input is connected
(E1213 only)
Off
EXT field power input is disconnected
I/O Wiring
Digital Inputs/Outputs
Analog Inputs/Outputs
– 5 –
Relay Output (Form A)
RTD Inputs
TC Inputs
System Configuration
Configuration via Web Console
Main configuration of an ioLogik E1200 is by web console.
Default IP Address: 192.168.127.254
Subnet Mask: 255.255.255.0
NOTE Be sure to configure the host PC's IP address to the same
subnet as the ioLogik E1200. For example,
192.168.127.253
ioSearch Utility
ioSearch is a search utility that helps users locate an ioLogik E1200
on the local network. The utility can be found in the Document and
Software CD  Software  ioSearch; the latest version can be
downloaded from Moxa's website.
– 6 –
Load Factory Default Settings
There are three ways to restore the ioLogik E1200 to factory default
settings.
1. Hold the RESET button for 5 seconds.
2. In the ioSearch utility, right-click on the ioLogik device to be
reset and select Reset to Default.
3. Select Load Factory Default from the web console.
Modbus Address Table
Consult the user's manual for the ioLogik's Modbus address, or find
the default address of the I/O channels in the web console by clicking
User-defined Modbus Addressing  Default Address.
Active OPC Server Connection
Connect the ioLogik E1200 to an Active OPC Server by following the
steps below:
1. Disable the user-defined Modbus address function.
2. Install the Active OPC Server Lite utility from the Document
and Software CD  Software  AOPC Lite 
ActiveOPCSetup  Install.exe.
3. Install from Web console  Active OPC Server Settings 
AOPC & I/O Settings; specify the IP address where the Active
OPC Server is installed. Specify the I/O channels that need to be
added to Active OPC Server Lite. Submit the settings and then
Save/Restart.
4. From Web Console  Active OPC Server Settings  Create
AOPC Tag, click the Create Tag button.
5. Launch Active OPC Server Lite from the Windows Start menu:
Start  Programs  MOXA  IOServer  ActiveOPC 
ActiveOPC. Save configurations before exiting Active OPC
Server Lite.
NOTE A "load" in a circuit schematic is a component or portion of
the circuit that consumes electric power. For the diagrams
shown in this document, "load" refers to the devices or
systems connected to the remote I/O unit.
– 7 –
www.moxa.com/support