Installation Overview

Caution!
Installation must be made by qualified personnel and conform to ANSI/NFPA 70 (the National
!
Electrical Code
and all applicable local codes. Bosch Security Systems, Inc. accepts no liability for any
damages or losses caused by incorrect or improper installation.
1. Select the mounting location.
Select a secure installation location and mounting position for the device. Ideally, this is a
location where the device cannot be interfered with either intentionally or accidentally.
4
5.1

Prepare Wiring

4
Maximum cable distance in meters (feet) per minimum cable diameter
The following table identifies the recommended transmission distance (maximum) in meters
(feet), based on the specified wattage, per the minimum cable diameter (in mm²), when the
cable diameter is fixed and the maximum permitted power consumption for 24 VAC is 10%.
For example, for a device of 20 W and a minimum cable diameter of 1.0 mm², the
recommended transmission distance is 42 m (141 feet) from the transformer.
Models
Indoor
(ceiling)
Outdoor
Wire Gage
Note: Metric wire sizes are standard DIN sizes, ISO6722, mm².
Wire diameter (mm²)
1.0
1.5
2.5
4.0
5.2

Prepare the Camera

1.
Bosch Security Systems
®
(NEC)), Canadian Electrical Code, Part I (also called CE Code or CSA C22.1),
Ensure that the selected mounting surface is capable of supporting the combined weight
of the camera and mounting hardware (sold separately) under all expected conditions of
load, vibration, and temperature.
Prepare and install all wiring for 24 VAC, PoE+ (Cat5e/Cat6), alarms, and audio as
necessary. For 24 VAC, follow the recommendations for maximum cable distance and
wire gage.
Watts
20
42 m (141 ft)
30
28 m (94 ft)
Loosen the three (3) Hex screws in the trim ring / bubble enclosure with the T15 Torx
screwdriver.
1.0 mm²
1.5 mm²
68 m (225 ft)
45 m (150 ft)
Installation Manual
Installation Overview | en
2.5 mm²
4.0 mm²
109 m (358 ft)
275 m (905 ft)
72 m (238 ft)
183 m (603 ft)
AWG
18
16
14
12
2015.11 | 1.1 |