7 GRT1-ECT Installation
7-2

Installation GRT1-ECT and Units

This section contains the procedures for installing the GRT1-ECT Unit and SmartSlice I/O Units.
7-2-1

Handling Precautions

When installing the EtherCAT Communication Unit and the SmartSlice I/O Units, observe the following

handling precautions

• Always turn OFF the power supply to the EtherCAT Communication Unit, the SmartSlice I/O Units
and the external I/O, before mounting or dismounting a Unit or connecting or disconnecting cables.
• Do not connect or disconnect the EtherCAT Communication Unit's communication cable while the
EtherCAT network is operational. Short-circuits or poor contacts in the EtherCAT cable may prevent
normal communication.
• Ensure that the power supplies for the EtherCAT Communication Unit and the SmartSlice I/O Units
and the external I/O are wired correctly.
• Provide separate conduits or ducts for the I/O and communication lines to prevent noise from
high-tension lines or power lines.
The SmartSlice I/O system is installed and set up as an EtherCAT Slave. The EtherCAT
Communication Unit's communication connector connects to the Master Unit through an EtherCAT
communication cable. Up to 64 SmartSlice I/O Units can be connected to one GRT1-ECT Unit.
EtherCAT
Master
EtherCAT
Communication Unit
OMRON
GRT1-ECT
x10
x10
24 VDC
for Unit
24 VDC
for I/O
7 - 6
Slide SmartSlice I/O Units
in from the front to install.
RUN
RUN
UNIT PWR
UNIT PWR
ERR
ERR
x1 x1
TS
TS
I/O PWR
I/O PWR
ON
ON
1
REGS
REGS
2
NC
NC
3
ADR
ADR
4
BACK
BACK
UNIT
UNIT
+V
+V
-V
I/O
+V
+V
-V -V
DC24V
DC24V
INPUT
INPUT
SmartSlice I/O Units (64 max.)
GX-series EtherCAT Slave Unit User's Manual