Section 4 Mounting; Checking Environmental Conditions And Mounting Space; Detaching And Installing The Plug-In Unit; Detaching The Plug-In Unit - ABB 615 Series Installation Manual

Ansi
Hide thumbs Also See for 615 Series:
Table of Contents

Advertisement

1MAC051065-MB C
Section 4
4.1
4.2
4.2.1
615 series ANSI
Installation Manual
Mounting
Checking environmental conditions and mounting
space
The mechanical and electrical environmental conditions at the installation site must be
within the limits described in the technical manual.
Avoid installation in dusty, damp places.
Avoid places susceptible to rapid temperature variations, powerful vibrations and
shocks, surge voltages of high amplitude and fast rise time, strong induced
magnetic fields or similar extreme conditions.
Check that sufficient space is available.
Sufficient space is needed at the front and rear of the IED to allow access to wires
and optical fibers and to enable maintenance and future modifications.
Flush mounted IEDs should be possible to be added or replaced without excessive
dismantling.

Detaching and installing the plug-in unit

Detaching the plug-in unit

Before detaching the plug-in unit from the case, the auxiliary voltage
must be disconnected.
1.
Turn off the power.
2.
Lift the lower handle until the spring-loaded locks on both sides of the handle are
released.
The unit is pushed about 0.25 inches (6 mm) out of the case and the connectors
are separated.
3.
Pull the unit out of the case.
Section 4
Mounting
13