Section 4
Mounting
20
Requirements for installation:
Panel cut-out of 6.52 x 6.36 inches (165.5 x 161.5 mm) with mounting holes
Depth behind the panel 4.06 inches (103 mm)
When IP 54 degree of protection (according to IEC 60529) is required for the front
side, a gasket has to be used in the installation.
1.
Mount the raising frame into the panel cut-out with four M4 screws.
A
B
D E
A070589 V2 EN
Figure 7:
Mounting the raising frame
A 6.83 inches (173.5 ±0.3 mm) 1 Panel
B 6.52 inches (165.5 ±1 mm)
C ∅ 0.22 inches (5.5 mm)
D 6.36 inches (161.5 ±1 mm)
E 5.24 inches (133 ±0.3 mm)
2.
Loosen the four M5 fixing screws in the case to fit the case to the raising frame.
3.
Mount the case to the raising frame.
C
1
2
3
2 Raising frame
3 M4 screw
1MAC051065-MB C
615 series ANSI