Danfoss ECL Comfort 110 User Manual, Installation & Maintenance page 7

Ecl comfort 110. weather compensated flow temperature control of heating and boiler systems
Hide thumbs Also See for ECL Comfort 110:
Table of Contents

Advertisement

Slope
Setting range
0.1 ... 4.0
Adjust the 'Slope' of the heat curve, if required.
The heat curve slope depends on the heating system and area specific design
parameters.
Example I
Design parameter:
Designed outdoor temperature (T
)
-12 °C
out
Designed flow temperature (T
)
80 °C
flow
Designed room temperature (T
)
20 °C
room
For designed flow temperature higher than 40 °C, the heat curve slope (S) can be
calculated as:
T
- 25
flow
S =
2.5 x T
- T
- 30
room
out
80 - 25
S =
2.5 x 20 - (- 12) - 30
S ≈ 1.7
Example II
Design parameter:
Designed outdoor temperature (T
)
-20 °C
out
Designed flow temperature (T
)
35 °C
flow
Designed room temperature (T
)
21 °C
room
For designed flow temperatures lower than 40 °C, the heat curve slope (S) can be
calculated as:
T
- 20
flow
S =
1.3 (2.5 x T
- T
- 30)
room
out
35 - 20
S =
1.3 (2.5 x 21 - (- 20) - 30)
S ≈ 0.3
For quick setting, the graph can be used. The graph is intended for a T
design data from example I is used, the slope will be approx. 1.7.
12
VI.KT.G2.02
2175
Factory setting
1.8
of 20 °C. If the
room
© Danfoss 05/2007
DH-SMT/DK
o
[
C]
150
2.2
2.6
3.0
3.5
4.0
140
1.8
130
120
110
1.4
100
90
1.0
80
70
0.6
60
0.4
50
0.3
40
0.2
30
0.1
20
10
-40
-30
-20
-10
How to determine another heat curve, if necessary:
Choose the calculated flow temperature for your system and the determined min.
outdoor temperature for your area. Pick the heat curve closest to the crossing point of
these two values.
The setting of the desired room temperature has an influence on the calculated flow
temperature (heat curve), no matter if a room temperature sensor is connected or not.
Floor heating systems
This controller is factory set for radiator systems, which typically are high flow temperature
systems. To control floor heating systems, which typically are low flow temperature systems,
you need to change the 'Slope' according to your type of system (typical setting: 1.0).
VI.KT.G2.02
DH-SMT/DK
o
[
C]
0
10
20
30
© Danfoss 05/2007