Total stop
Setting range
ON / OFF
Decide whether you want a total stop during the setback temperature period.
ON:
The desired system temperature is lowered to 'Standby T' (line 7093).
'Temp. min.' (line 2177) is overruled.
Desired system temp. °C
'Standby T'
OFF:
No total stop
Desired system temp. °C
'Standby T'
S1 T filter (outdoor temp. filter)
Setting range
1 ... 200
Dampens the measured outdoor temperatures by the set factor.
1:
Fast (low filter constant)
200:
Slow (high filter constant)
24
VI.KT.G2.02
5021
Factory setting
OFF
Time
Time
5081
Factory setting
100
© Danfoss 05/2007
DH-SMT/DK
Cut-out (limit for heating cut-out)
Setting range
OFF / 1 ... 50 °C
Set the outdoor temperature limit at which you want the heating system to stop. The
valve closes and after about 3 min. the heating circulation pump stops. 'Temp. min.'
set in line 2177 will be ignored.
Temp.
Actual outdoor temp. Accumulated outdoor temp.
18 °C
Heating
Heating OFF
This function can save energy by stopping the heating system when the outdoor
temperature gets above a set limit. The heating system switches ON again when the
outdoor temperature and the accumulated outdoor temperature become lower than
the set limit.
The heating cut-out is only active when the controller mode is AUTO (scheduled operation).
When the limit value is set to OFF, there is no heating cut-out.
VI.KT.G2.02
DH-SMT/DK
5179
Factory setting
18 °C
Time
Heating
© Danfoss 05/2007