Parameter
MaxTsdr_12M
Redundancy
Repeater_Ctrl_Sig
24V_Pins
Freeze_Mode_supp
Sync_Mode_supp
Auto_Baud_supp
Set_Slave_Add_supp
Min_Slave_Intervall
Modular_Station
Max_Module
Max_Input_Len
Max_output_Len
Max_Data_Len
Fail_Safe
Max_Diag_Data_Len
Slave_Family
PrmText
Text(0)
Text(1)
EndPrmText
Value
Longest time 800 bit times at communication speed
800
12.0Mbps
0
Redundancy not supported.
2
Installed as TTL level via RTS signal from module.
24V power supply for maintenance device connection is not
0
used.
1
Freeze mode supported.
1
Synchronous mode supported.
1
Automatic baud rate detection support
0
Slave address is not set.
100 µs interval between 2 polling cycles
1
1
Modular device specified.
1
Maximum number of modules:1
28
Input data: Maximum 28 bytes
28
Output data: Maximum 28 bytes
56
Input and output data: Maximum 28 + 28 = 56 bytes
0
Failsafe not supported
6
Diagnostic data of 6 bytes secured (no external diagnosis)
1
Drives defined as function class (Main Family)
1
Text selection 1 registration
"No byte swapping"
If Bit 0 = 0, "No byte swapping"
"Byte swapping"
If Bit 0 = 1, "Byte swapping"
PROFIBUS DEVICE DATA
Description
*1
6
39