Fujitsu ARTG30LHTA Service Instruction page 56

Duct type inverter indoor / outdoor unit, refrigerant r410a
Hide thumbs Also See for ARTG30LHTA:
Table of Contents

Advertisement

Trouble shooting 23
OUTDOOR UNIT Error Method:
4-Way Valve Error
Detective Actuators:
Indoor Unit Controller PCB Circuit
Heat Exchanger Temperature Thermistor
Room Temperature Thermistor
4-way valve
Forecast of Cause :
1. Connector connection failure
5. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Check thermistor of Indoor unit
Isn't it fallen off the holder?
Is there a cable pinched?
>> Check characteristics of thermistor, (Refer to Trouble shooting 5,6),
If defective, replace the thermistor.
OK
OK
Check Point 3 : Check the solenoid coil and 4-way valve
[ Solenoid coil ]
Remove CN111 from PCB and check the resistance value of coil.
Resistance value is about 1.4k
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[ 4-way valve ]
Check each piping temperature,
and the location of the valve by the temperature difference.
>> If the value location is not proper, replace 4-way valve.
OK
OK
Check Point 4 : Replace Main PCB
If Check Point 1- 3 do not improve the symptom, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When the indoor heat exchanger temperature is compared with
the room temperature, and either following condition is detected
continuously two times, the compressor stops.
Cooling or Dry operation
[Indoor heat exchanger temp.] - [Room temp.] > 20degC
Heating operation
[indoor heat exchanger temp.] - [Room temp.] < -14degC
If the same operation is repeated 5 times,
the compressor stops permanently.
2. Thermistor failure
3. Coil failure
02-26
4. 4-way valve failure

Advertisement

Table of Contents
loading

Table of Contents