Fujitsu ARTG30LHTA Service Instruction page 41

Duct type inverter indoor / outdoor unit, refrigerant r410a
Hide thumbs Also See for ARTG30LHTA:
Table of Contents

Advertisement

Trouble shooting 8
INDOOR UNIT Error Method:
Drainage Error
Detective Actuators:
Indoor Unit Controller PCB Circuit
Float Switch
Forecast of Cause : 1. Float switch failure 2. Shorted connector/wire 3. Controller PCB failure
4. Drain pump failure 5. Hose clogging
Check Point 1 : Check Float Switch
Check operation of float switch. (any blocking by dust, etc.)
Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is abnormal, replace it.
OK
Check Point 2 : Check Connector and Wire
Check loose contact of
CN000(ARTG30/36LHTA)
CN000(ARTG45/54LHTA)
>>Replace Float switch if the wire is abnormal
OK
Check Point 3 : Check Drain Hose
Check Drain Hose .
>>If there is Hose clogging. Please clear the clog.
OK
Check Point 4 : Check Controller PCB
If Check Point 1 ~ 3 do not improve the symptom, change
Controller PCB and execute the check operation again.
Indicate or Display:
Refer to error code table.
Detective details:
When Float switch is ON for more than 3 minutes.
/
and shorted wire (pinched wire).
ON
Attention!!
Wall mount / Small size wall mount type
does not have a float switch.
In this case, replace
and set up the original address.
Please refer to.
02-11
OFF
PCB
Controller