Fujitsu ARTG30LHTA Service Instruction page 24

Duct type inverter indoor / outdoor unit, refrigerant r410a
Hide thumbs Also See for ARTG30LHTA:
Table of Contents

Advertisement

Trouble shooting 18
OUTDOOR UNIT Error Method:
Pressure Sencer Error
Detective Actuators:
High pressure switch
Forecast of Cause :
1. High pressure switch connector disconnection, open
2. High pressure switch characteristics failure3. Main PCB failure
Check Point 1 : Check the high pressure switch connection state
Connector and wiring connection state check
Cable open check
OK
Check Point 2 : Check the high pressure switch characteristics
Switch characteristics check
* For the characteristics of high pressure switch, refer to below.
OK
Check Point 3 : Replace Main PCB
, and execute the check operation again.
Change Main PCB
Type of contact
C
H
Pressure
Characteristics of pressure switch
Contact : Short
Open
Contact : Open
Short
Indicate or Display:
Refer to error code table.
Detective details:
When the power was turned on, "high pressure switch : open" was detected.
(CN101)
Pressure switch 1
4.2 0.1MPa
3.2 0.15MPa
02-21