Product Specification - Sena Rhio10 User Manual

Remote i/o manager
Table of Contents

Advertisement

1.3 Product Specification

Network Interface
Digital Input
Digital Output
Analog Input
Protocol
Management
Software Support
Diagnostic LED
Power
Environmental
10 Base-T Ethernet with RJ45 Ethernet connector
Supports static and dynamic IP address
-Number of channels: 12
-Input type: Voltage
-Input circuitry: Optically isolated photo-coupler
-Input range: 0V ∼ ±24V
OFF 0V ∼ ±1.2V, ON ±3.3V ∼ ±24V
-Sampling rate: 20ms
-Isolation voltage: 5KV
- Number of channels: 10
- Output type: Relay
- Rated load: 3A/240VAC
- Insulation resistance: 1000㏁ Min (DC500V)
- Isolation voltage(coil and contact): 4KV
- Reaction within 10ms
- Number of channels: 4
- Effective resolution: 10-bit
- Input type: Voltage, Direct Coupling
- Input range: 0V ∼ Aref (Analog reference voltage, 2~5V)
- Sampling rate: 1000 samples/sec
ARP, IP/ICMP, TCP
telnet, DHCP client, PPPoE
- Rhio Manager Windows Utility, Serial Console or Telnet
- Windows MFC DLL library
- I/O configuration, I/O status monitoring/control
- Power, Link, Act
- Digital Output, 1~10
- Digital Input, 1~12
- Analog Input, 1~4
9V∼48VDC, Max. 5W
- Operating temperature: 0℃ to 50℃
- Storage temperature: -20℃ to 66℃
- 90% Non-condensing