5.2 PRODUCT SETUP
These settings are applicable to fixed (DNA/UserSt) GOOSE only.
The
setting represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE
GOOSE ID
message. This string identifies the GOOSE message to the receiving device. In revisions previous to 5.0x, this name string
was represented by the
The
DESTINATION MAC
address; the least significant bit of the first byte must be set. In B90 releases previous to 5.0x, the destination Ethernet
MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of
the B90) and setting the multicast bit.
The
GOOSE VLAN PRIORITY
have higher priority than other Ethernet data. The
ID for each GOOSE sending device. This value can be left at its default if the feature is not required. Both the
and
PRIORITY
GOOSE ETYPE APPID
The configurable GOOSE settings are shown below.

PATH: SETTINGS...
COMMUNICATIONS
 CONFIGURABLE
 GOOSE 1
5
The configurable GOOSE settings allow the B90 to be configured to transmit a number of different datasets within IEC
61850 GOOSE messages. Up to eight different configurable datasets can be configured and transmitted. This is useful for
intercommunication between B90 IEDs and devices from other manufacturers that support IEC 61850.
The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the B90.
The B90 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data
transfer between devices.
Items programmed for dataset 1 and 2 will have changes in their status transmitted as soon as the change is detected.
Datasets 1 and 2 should be used for high-speed transmission of data that is required for applications such as transfer trip-
ping, blocking, and breaker fail initiate. At least one digital status value needs to be configured in the required dataset to
enable transmission of configured data. Configuring analog data only to dataset 1 or 2 will not activate transmission.
Items programmed for datasets 3 through 8 will have changes in their status transmitted at a maximum rate of every
100 ms. Datasets 3 through 8 will regularly analyze each data item configured within them every 100 ms to identify if any
changes have been made. If any changes in the data items are detected, these changes will be transmitted through a
GOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent.
For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if no
changes in the data items are detected.
5-20
setting.
RELAY NAME
setting allows the destination Ethernet MAC address to be set. This address must be a multicast
setting indicates the Ethernet priority of GOOSE messages. This allows GOOSE messages to
GOOSE ETYPE APPID
settings are required by IEC 61850.

IEC 61850...
CONFIG GSE 1
FUNCTION: Enabled
CONFIG GSE 1 ID:
MESSAGE
GOOSEOut_1
CONFIG GSE 1 DST MAC:
MESSAGE
010CDC010000
CONFIG GSE 1
MESSAGE
VLAN PRIORITY: 4
CONFIG GSE 1
MESSAGE
VLAN ID:
CONFIG GSE 1
MESSAGE
ETYPE APPID:
CONFIG GSE 1
MESSAGE
CONFREV:
CONFIG GSE 1 RESTRANS
MESSAGE
CURVE: Relaxed
 CONFIG GSE 1
MESSAGE
 DATASET ITEMS
B90 Low Impedance Bus Differential System
setting allows the selection of a specific application

GSSE...
TRANSMISSION
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address
Range: 0 to 7 in steps of 1
Range: 0 to 4095 in steps of 1
0
Range: 0 to 16383 in steps of 1
0
Range: 0 to 4294967295 in steps of 1
1
Range: Aggressive, Medium, Relaxed, Heartbeat
Range: 64 data items; each can be set to all valid MMS
data item references for transmitted data
5 SETTINGS
GOOSE VLAN
CONFIGURABLE GOOSE 1(8)