Front Panel User Interface; Mounting Methods - ABB REM630 Product Manual

Relion 630 series motor protection and control
Hide thumbs Also See for REM630:
Table of Contents

Advertisement

ABB
Motor Protection and Control
REM630
Product version: 1.1
19. Front panel user
interface
The 630 series IEDs can be ordered with an
detached front-panel user interface (HMI). An
integrated HMI is available for 4U high
housing. The local HMI includes a large
graphical monochrome LCD with a resolution
of 320 x 240 pixels (width x height). The
amount of characters and rows fitting the
view depends on the character size as the
characters' width and height may vary.
In addition, the local HMI includes dedicated
open/close operating buttons and five
Figure 4. Local user interface

20. Mounting methods

By means of appropriate mounting
accessories the standard IED case for the 630
series IEDs can be flush mounted, semi-flush
mounted or wall mounted. Detachable HMI is
intended for optimized mounting in medium
voltage metal-clad switchgear, thus reducing
wiring between the low-voltage compartment
and the panel door. Further, the IEDs can be
mounted in any standard 19" instrument
cabinet by means of 19" rack mounting
accessories.
For the routine testing purposes, the IED
cases can be installed with RTXP test
programmable function buttons with LED
indicators. The 15 programmable alarm LEDs
can indicate a total of 45 alarms. The local
HMI offers full front-panel user-interface
functionality with menu navigation, menu
views and operational data. In addition, the
local HMI can, using PCM600, be configured
to show a single-line diagram (SLD). The SLD
view displays the status of the primary
apparatus such as circuit breakers and
disconnectors, selected measurement values
and busbar arrangements.
GUID-5CFD3446-A92F-4A5F-B60D-90025DCFDC61 V2 EN
switches (RTXP8, RTXP18 or RTXP24) which
can be mounted side by side with the IED
case in a 19" rack.
Mounting methods:
• Flush mounting
• Semi-flush mounting
• Overhead/ceiling mounting
• 19" rack mounting
• Wall mounting
• Mounting with a RTXP8, RTXP18 or
RTXP24 test switch to a 19"rack
• Door mounting of the local HMI, IED case
mounted in the low-voltage compartment of
the switchgear
1MRS756977 D
Issued: 2011-05-18
55