ABB REM630 Product Manual page 25

Relion 630 series motor protection and control
Hide thumbs Also See for REM630:
Table of Contents

Advertisement

ABB
Motor Protection and Control
REM630
Product version: 1.1
Table 24. Electromagnetic compatibility tests, continued
Description
Power frequency immunity
test
• Common mode
• Differential mode
Voltage dips and short
interruptions
Electromagnetic emission
tests
• Conducted, RF-emission
(mains terminal)
0.15...0.50 MHz
0.5...30 MHz
• Radiated RF-emission
30...230 MHz
230...1000 MHz
Type test value
Binary inputs only
300 V rms
150 V rms
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
< 79 dB(µV) quasi peak
< 66 dB(µV) average
< 73 dB(µV) quasi peak
< 60 dB(µV) average
< 40 dB(µV/m) quasi peak,
measured at 10 m distance
< 47 dB(µV/m) quasi peak,
measured at 10 m distance
1MRS756977 D
Issued: 2011-05-18
Reference
IEC 60255-22-7, class A
IEC 61000-4-16
IEC 61000-4-11
EN 55011, class A
IEC 60255-25
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents