18. Technical data

Table 7. Dimensions
Description
Width
Height
Depth
Weight box
Weight LHMI
1) Without LHMI
Table 8. Power supply
Description
U
nominal
aux
U
variation
aux
Maximum load of auxiliary
voltage supply
Ripple in the DC auxiliary
voltage
Maximum interruption time in
the auxiliary DC voltage
without resetting the IED
Power supply input must be
protected by an external
miniature circuit breaker
Value
220 mm
177 mm (4U)
265.9 mm (6U)
249.5 mm
6.2 kg (4U)
5.5 kg (6U)
1.0 kg (4U)
Type 1
100, 110, 120, 220, 240 V
AC, 50 and 60 Hz
110, 125, 220, 250 V DC
85...110% of U
(85...264 V
n
AC)
80...120% of U
(88...300 V
n
DC)
35 W
Max 15% of the DC value (at frequency of 100 Hz)
50 ms at U
aux
For example, type S282 UC-K.
The rated maximum load of aux voltage which is given as
35 watts. Depending on the voltage used, select a suitable
MCB based on the respective current. Type S282 UC-K has
a rated current of 0.75 A at 400 V AC.
1MRS756977 D
Issued: 2011-05-18
1)
Type 2
48, 60, 110, 125 V DC
80...120% of U
(38.4...150 V
n
DC)
17