Table 24. Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst
disturbance test
• Common mode
• Differential mode
Electrostatic discharge test
• Contact discharge
• Air discharge
Radio frequency interference
tests
• Conducted, common mode 10 V (rms), f=150 kHz...80
• Radiated, pulse-modulated
• Radiated, amplitude-
modulated
Fast transient disturbance
tests
• All ports
Surge immunity test
• Communication
• Binary inputs, voltage
inputs
• Other ports
Power frequency (50 Hz)
magnetic field
• 1...3 s
• Continuous
24
Type test value
2.5 kV
1.0 kV
8 kV
15 kV
MHz
10 V/m (rms), f=900 MHz
10 V/m (rms), f=80...2700
MHz
4 kV
1 kV line-to-earth
2 kV line-to-earth
1 kV line-to-line
4 kV line-to-earth, 2 kV line-
to-line
1000 A/m
300 A/m
1MRS756977 D
Issued: 2011-05-18
Reference
IEC 61000-4-18
IEC 60255-22-1, level 3
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3.2001
IEC 61000-4-6
IEC 60255-22-6, level 3
ENV 50204
IEC 60255-22-3
IEC 61000-4-3
IEC 60255-22-3, level 3
IEC 61000-4-4
IEC 60255-22-4, class A
IEC 61000-4-5
IEC 60255-22-5
IEC 61000-4-8
ABB