ABB REM630 Product Manual page 16

Relion 630 series motor protection and control
Hide thumbs Also See for REM630:
Table of Contents

Advertisement

Motor Protection and Control
REM630
Product version: 1.1
IEC 60870-5-103 is available from optical
serial port where it is possible to use serial
glass fibre (ST connector) or serial plastic
fibre (snap-in connector).
The IED supports SNTP, DNP3 and IRIG-B
time synchronization methods with a time-
stamping resolution of 1 ms.
The IED supports the following time
synchronization methods with a
timestamping resolution of 1 ms:
Table 6. Supported communication interface and protocol alternatives
Interfaces/
1)
100BASE-TX
protocols
IEC 61850
DNP3
IEC 60870-5-103
● = Supported
1) Please refer to the Selection and ordering data chapter for more information
16
Ethernet
Ethernet
100BASE-FX LC
RJ-45
Ethernet communication based:
• SNTP (simple network time protocol)
• DNP3
With special time synchronization wiring:
• IRIG-B (Inter-Range Instrumentation Group
- Time Code Format B)
IEC 60870-5-103 serial communication has a
time-stamping resolution of 10 ms.
Serial snap-in
1MRS756977 D
Issued: 2011-05-18
Serial ST
ABB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents