Table 31. Three-phase non-directional overcurrent protection (PHxPTOC) main settings
Parameter
Start Value
Time multiplier
Operate delay time
Operating curve
1)
type
1) For further reference please refer to the Operating characteristics table
Function
PHLPTOC
PHHPTOC
PHIPTOC
PHLPTOC
PHHPTOC
PHLPTOC
PHHPTOC
PHIPTOC
PHLPTOC
PHHPTOC
PHIPTOC
Value (Range)
Step
0.05...5.00 pu
0.01
0.10...40.00 pu
0.01
0.10...40.00 pu
0.01
0.05...15.00
0.05
0.05...15.00
0.05
0.04...200.00 s
0.01
0.02...200.00 s
0.01
0.02...200.00 s
0.01
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12,
13, 14, 15, 17, 18, 19
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
Definite time
1MRS756977 D
Issued: 2011-05-18
29