ABB REM630 Product Manual page 21

Relion 630 series motor protection and control
Hide thumbs Also See for REM630:
Table of Contents

Advertisement

ABB
Motor Protection and Control
REM630
Product version: 1.1
Table 14. Power output relays with TCS function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit
time constant L/R<40 ms, at U< 48/110/220
V DC
Minimum contact load
Control voltage range
Current drain through the supervision circuit
Minimum voltage over the TCS contact
Table 15. mA outputs
Description
mA outputs
Output range
Operation accuracy
Maximum (including wiring resistance)
Hardware response time
Isolation
Table 16. Ethernet interfaces
Ethernet interface
LAN1 (X1)
Table 17. Fibre-optic communication link
Wave length
Fibre type
1300 nm
MM 62.5/125
μm glass
fibre core
1) Maximum allowed attenuation caused by connectors and cable together
Protocol
TCP/IP protocol
Connector
LC
Value
250 V DC
8 A
15 A
30 A
≤1 A/≤0.3 A/≤0.1 A
100 mA at 24 V DC
20...250 V DC
~1.0 mA
20 V DC
Value
-20 mA ... +20 mA
±0.2 mA
700 Ω
~80 ms
4 kV
Cable
Fibre-optic cable
with LC connector or
shielded twisted pair
CAT 5e cable or better
Permitted path
1)
attenuation
<8 dB
1MRS756977 D
Issued: 2011-05-18
Data transfer rate
100 MBits/s
Distance
2 km
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents