Fault
Fault
Fault name
code
ID
Process supervi-
101
1101
sion fault (PID1)
Process supervi-
105
1105
sion fault (PID2)
1109
Input pressure
109
supervision
1409
1315
Temperature
111
fault 1
1316
1317
Temperature
112
fault 2
1318
Service support: find your nearest Vacon service center at www.vacon.com
Possible cause
PID controller: Feedback value outside
of supervision limits (and the delay if
set).
PID controller: Feedback value outside
of supervision limits (and the delay if
set).
Input pressure supervision signal has
gone below the alarm limit.
Input pressure supervision signal has
gone below the fault limit.
At least one of the selected tempera-
ture input signals has reached the
alarm limit.
At least one of the selected tempera-
ture input signals has reached the fault
limit.
At least one of the selected tempera-
ture input signals has reached the fault
limit.
At least one of the selected tempera-
ture input signals has reached the fault
limit.
Table 32. Fault codes and descriptions.
vacon • 100
Remedy
Check settings.
Check settings.
Check the process.
Check the parameters
Check the input pressure sen-
sor and connections.
Find the cause of temperature
raise.
Check the temperature sensor
and connections.
Check that the temperature
input is hard wired if no sensor
is connected.
See option board manual for
further information.