5.4 Network 1
Definition: Network 1 = RS485 to expand inputs
5.4
Time out (mS)
Attempts
Alarm time (S)
Network 1 & 2
Menu available for models with RS485 only
From this menu, you can set the operating parameters for Network 1.
See the self-configuration procedure too:
• Timeout (ms) : value of the timeout for the response from controllers.
• Attempts : from 0 to 3 = number of times the Televis slave tries to send data
before generating a 'No-Lnk' error (value 0=one attempt, 3=four attempts).
• Alarm time (s) (Network 1 & 2) : values from 10 to 300 seconds in 10-second
steps = sets the frequency with which the Datalogger runs a full network scan
of alarm states in each resource.
5.5 Not used
9MA10011
NETWORK PARAMETERS
640
3
30
5.6 Network 3
Definition: Network 3 = RS232 port to download data
5.6
Network type:
Baud Rate
Slave 210 address
Menu available for models with RS232 only
From this menu, you can set the communication network for Network 3:
To ensure the data download software runs correctly, leave the original
configuration as shown in the example.
5.7 Not used
5.8 Passwords
See user interface chapter
5.9 Not used
NETWORK PARAMETERS
Modbus Slave
19200
24/52