4.4.1 Analogue Inputs

This menu shows the list of onboard analogue inputs.
4.4.1 ANALOGUE INPUTS
01
02
03
04
05
06
07
08
Select the required analogue input using the UP and DOWN keys and press OK.
A page displaying the following information will open:
(example Index 01 Input, pressure probe).
4.4.1 ANALOGUE INPUTS
Index
Name
Probe type
Unit of measure Bar
Decimal points
Value = 04mA
9MA10011
ONBOARD-P1
ONBOARD-P2
ONBOARD-P3
ONBOARD-P4
ONBOARD-P5
ONBOARD-P6
ONBOARD-P7
ONBOARD-P8
1/8
ONBOARD-P1
4..20mA
1
0.0
Value = 20mA
Offset
Read
View Text
|
• Index: Input Index***
|
• Name: Name of Input. The default names are ONBOARD-P1 .. ONBOARD-P8
|
and can be modified as required (max. 10 characters)
|
• Probe type: set automatically between [ 4...20mA and NTC 103AT]
• Unit of Measure : see Units of Measure table
|
• Decimal Points : values [0...3] for 4..20mA, [0...1] for NTC
|
• If Probe Type = 4...20 mA :
|
- Value = 04 mA: indicates start of scale
- Value = 20 mA indicates full scale
• If Probe Type = NTC :
• Minimum Value***
• Maximum Value***
• Offset: Probes Calibration. Note: the modification on the Value Read (see next
item) is immediate.
• Read Value read in real time***
• View Text : if YES then the value is entered in a list of elements to be viewed in
Default View.
|
*** Read-only information.
|
|
|
|
|
30.0
0.7
13.3
YES
|
|
|
16/52