4.4.2 Analogue alarms

This menu shows the list of onboard analogue inputs.
4.4.2 ANALOGUE ALARMS
01
02
03
04
05
06
07
08
Select the required analogue input using the UP and DOWN keys and press OK.
A page displaying the following information will open:
(example Index 01 Input, pressure probe)
4.4.2 ANALOGUE ALARMS
Index
Name
Alarm Output
Delay (min)
Positiv. Emerg.
Positiv. Delay
Negativ. Emerg.
Negativ. Delay
Alarm Hysteresis
9MA10011
ONBOARD-P1
ONBOARD-P2
ONBOARD-P3
ONBOARD-P4
ONBOARD-P5
ONBOARD-P6
ONBOARD-P7
ONBOARD-P8
1/8
ONBOARD-P1
1
0
10.0
8.0
0.0
0.0
0.1
• Index: Input Index***
• Name: Name of Input***
• Alarm Output : 0=none associated; 1=Output 1;
• Delay (min): minutes delay before activating Alarm Output [0...240 min]
• Positiv. Emerg: upper threshold and immediate generation of alarm when
limit exceeded
|
• Positiv. Delay: upper threshold and delayed generation of alarm when limit
|
exceeded
- NOTE: Positiv. Emerg. > Positiv. Delay
|
• Negativ. Delay: lower threshold and delayed generation of alarm when lower
|
limit exceeded
|
• Negativ. Emergency: lower threshold and immediate generation of alarm
|
when lower limit exceeded
|
- NOTE: Negativ. Emerg. < Positiv. Delay
• Alarm Hysteresis: Alarm reset hysteresis.
*** Read-only information.
Notice : alarm thresholds and hysteresis values are expressed in the units of
measure listed above (point 4.4.1 for the Analogue Input).
|

4.4.3 Digital Inputs

|
This menu shows the list of onboard digital inputs.
|
|
|
|
01
|
02
|
4.4.3 DIGITAL INPUTS
ONBOARD-D1
ONBOARD-D2
17/52