Step 3: Connect; Programming The Datalogger To Save Data To The Compactflash ® Card; Setup Screen (Ez View) Datalogger Settings - Campbell NL116 Instruction Manual

Ethernet and compactflash module
Table of Contents

Advertisement

d. Input the PakBus Address of the datalogger.
FIGURE 4-6. Setup screen (EZ View) Datalogger Settings
e.

4.2.3 Step 3: Connect

You are now ready to connect to your datalogger using the LoggerNet Connect
screen.
Datalogger program transfer, table-data display, and data collection are now
possible.
4.3
Programming the Datalogger to Save Data to the
CompactFlash
The CardOut() instruction is used in the datalogger program to send data to
the CF card. CardOut() must be entered within each DataTable declaration
that is to store data on the CF card. The file is saved on the card with the name
stationname.tablename and a .DAT extension.
The CardOut() instruction has the following parameters:
StopRing: A constant is entered for the StopRing parameter to specify whether
the DataTable created should be a ring-mode table (0) or a fill-and-stop table
(1).