Regency Fireplace Products Greenfire GFi350LNG-R Owners & Installation page 18

Gas inbuilt fireplaces
Table of Contents

Advertisement

installation
13. Reinstall new burner orifice LPG stamped #53 or ULPG burner orifice
stamped #55 and tighten.
14. Install new LP burner supplied with kit ensuring aeration is set to 13mm
for LPG or fully open for ULPG - prior to install.
15. Replace the yellow "NG" label with the red "ULPG" label.
16. Carefully pull out the control box.
NOTE: The control box is held in place with velcro.
17. Remove the heat shield from the control box by removing the 2 screws.
18. Remove the control box cover by undoing the 3 screws.
Manoeuvre through antenna.
19. Remove the jumper using pliers and discard.
Jumper
20. Reverse Steps 18, 17,16, 9, 8, 7, 6, and 5.
21. Turn on gas supply and plug in power cord.
22. Adjusting the Outlet Pressure
All the adjustments must be carried out in the following order:
Installer Notice:
These instructions must be left
with the appliance.
18
Antenna
Control Box
Cover
Jumper Location
Remove the modulator plastic cap (A) using needle nose pliers.
Maximum pressure: Turn the unit ON to its highest input rating. Screw
in the nut (B) to increase the outlet pressure and screw it out to decrease
it. Use a 10 mm wrench.
NOTE: The outlet pressure for LPG or ULPG must be set to maximum 2.3
kPa.
Minimum pressure: Remove one of the cables connected to the electric
modulator. While holding the nut (B) with a wrench, screw in the screw (C)
to increase the pressure and screw it out to decrease it. Use a screwdriver
6 x 1 blade.
After carrying out all adjustments, block the setting screws with
paint, taking care not to obstruct the breather orifice of the pres-
sure.
Put back the modulator plastic cap.
WARNING: To ensure the correct operation of the modulator it is
necessary that the plastic cap (A) is returned to its original loca-
tion.
NOTE: The outlet pressure for LPG or ULPG must be set to minimum 1.5 kPa.
Manifold Pressure (High)
Manifold Pressure (Low)
B
23. Reverse Steps 10,4,3,2 and 1.
24. At the end of all setting and adjustment operations, check electrical
installation and gas leaks.
24. Check operation of flame control.
25. Check for proper flame appearance and glow on logs.
Cable
Electric
Modulator
LPG
ULPG
2.30 kPa
2.30 kPa
1.50 kPa
1.50 kPa
A
C
Regency GFi350L Gas Fireplace Inbuilt