installation

GAS CONNECTION

GAS CONNECTION WARNING:
Only persons licensed to work with gas piping may make the
necessary gas connections to this appliance.
1. If the appliance is to be installed into an existing chimney system, thoroughly
clean the masonry or factory built fireplace.
2. The gas connection is 1/2" BSP.
3. Locate the center point where the flue will pass through the chimney above
the appliance. Move the appliance into the exact location where it is to be
installed. Ensure that the Insert is level.
4. The installer must provide a valve with a plugged tapping, accessible for
test gauge connection, immediately upstream of the gas supply connection
to the appliance.
CAUTION: If the glass is removed or opened for servicing, it must be
replaced and closed prior to operating the appliance. The glass must be
fixed in the door when operating.
SPECIFICATIONS
NG
LP
Injector
#40
#53
Size
2.50mm
1.50mm
Input
Max. 30 mj
Max. 27 mj
Rating
Min. 20mj
Min. 22 mj
Manifold
High 0.9 kPa
High 2.3 kPa
Pressure
Low 0.42 kPa
Low 1.50 kPa
Aeration
5 mm
13 mm
Setting
14
ULPG
#55
1.30mm
Max. 21 mj
Min. 17 mj
High 2.3 kPa
Low 1.50 kPa
Full open
Regency GFi350L Gas Fireplace Inbuilt