5.3

Connection Diagram

Representative wiring examples are shown in this section. When pin numbers in the counterpart equipment are different, wire
the pins as shown below.

Connection diagram for RS-232C

Name
FG
RD (RXD)
SD (TXD)
ER (DTR)
SG (GND)
DR (DSR)
*1 For third-party external equipment requiring the control signal, connect these pins.
The FX5-232-BD, FX5-232ADP does not require these pins to be connected.

Connection diagram for RS-485

One-pair wiring
Master
built-in RS-485 port
FX5-485-BD
FX5-485ADP
SDA
(TXD+)
SDB
Termination
(TXD-)
resistor:
110 
RDA
*2
(RXD+)
RDB
(RXD-)
SG
Class-D grounding
(resistance: 100  or less)
*1 Make sure to perform Class-D grounding on the shield of the twisted pair cable to be connected.
*2 Make sure to provide a termination resistor at each end of a line. Set the selector switch to 110  when the termination resistor is built in.
PLC
FX5-232-BD
FX5-232ADP
Name
9-pin D-Sub
-
FG
2
RD (RXD)
3
SD (TXD)
4
RS (RTS)
5
SG (GND)
*1
6
CS (CTS)
Slave
built-in RS-485 port
FX5-485-BD
FX5-485ADP
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SG
Class-D grounding
(resistance: 100  or less)
*1
External equipment operating in
accordance with RS-232C
Using CS and RS
Using DR and ER
Name
D-Sub
D-Sub
D-Sub
9-pin
25-pin
9-pin
-
1
FG
-
2
3
RD (RXD)
2
3
2
SD (TXD)
3
7
4
ER (DTR)
4
5
7
SG (GND)
5
8
DR (DSR)
5
6
Slave
built-in RS-485 port
FX5-485-BD
FX5-485ADP
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SG
Class-D grounding
(resistance: 100  or less)
*1
D-Sub
25-pin
1
3
2
20
7
6
Slave
built-in RS-485 port
FX5-485-BD
FX5-485ADP
SDA
(TXD+)
SDB
(TXD-)
Termination
resistor:
110 
RDA
*2
(RXD+)
RDB
(RXD-)
SG
*1