Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 64

Modbus communication
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Operation error
■Error flags
The operation error flag turns ON when an operation error occurs in the ADPRW instruction.
Verify that the device specified in the table below is ON.
FX5 dedicated
CH1
CH2
CH3
SM0
SM1
SM56, SM8067
■Error codes
When the operation error flag turns ON, the error code (hexadecimal) is stored in the operation error code (SD0/SD8067).
The error codes stored in the device are shown as follows.
Error code
Description
1810H
Channel double use
3600H
Invalid parameter setup
2822H
A device was specified that cannot be
specified with the instruction.
3405H
Data was entered outside of the range that
can be specified.
2820H
A device or label was beyond the range that
can be specified with the instruction.
APPX
62
Appendix 2 Error code
Name
CH4
Latest self-diagnostic error
(Including the annunciator ON)
Latest self-diagnostic error
(Not including the annunciator ON)
Operation error
Description
Turns ON when an operation error occurs.
Details
Channel used by the instruction is used by another instruction.
The instruction is used in Slave mode.
Wrong operand set for the instruction.
The operand device number range or data value set for the
instruction is out of range.
The operand corresponding device set for the instruction is out of
range.
Error station
Master/Slave
Slave
Master
Master
Master

Hide quick links: