ComAp IG-NT Reference Manual page 12

Inteli new technology modular gen-set controller single parallel to mains – sw configuration sptm
Hide thumbs Also See for IG-NT:
Table of Contents

Advertisement

Load reconnection – automatic -> AutoLd recon = ENABLED
Gen-set power
Ld recon level
BO Load shed 3
BO Load shed 2
BO Load shed 1
Ld recon del
Load reconnection – manual -> AutoLd recon = DISABLED
Test on load – SPtM
Affects the behavior in TEST mode. Before the activation of this function
1. adjust setpoint AMF settings: ReturnTo mains = DISABLED
2. adjust Process control: MFStart enable = YES.
3. switch controller to Test on load mode (see drawing below)
Gen-set starts and goes to load (synchronizes to the mains, closes GCB and opens MCB) automatically
when this input is closed even if Mains is OK.
Inteli NT SPtM, SW Version 2.4, ©ComAp –December 2009
IGS-NT-SPtM-2.4-Reference Guide.PDF
opened
opened
Ld recon del
Ld recon del
opened
12