Sullair 3000PB User Manual page 41

40, 50 & 60 hp (30, 37 & 45 kw)
Table of Contents

Advertisement

3.12 Wiring diagram, air-cooled MFV
Component Description
1MOL
COMPRESSOR OVERLOAD
1M
COMPRESSOR STARTER
2MOL
FAN MOTOR OVERLOAD
P1
WET SUMP PRESSURE SENSOR
P2
PACKAGE DISCHARGE PRESSURE SENSOR
T1
UNIT DISCHAGE TEMPERATURE PROBE
PSW1
(OPT'L)INLET AIR FILTER SWITCH 558.9 MM WC - 22 IN WC
DPSW1
(OPT'L)OIL FILTER DIFF PRESS SWITCH 20PSID
INPUT 7
REMOTE RUN/UNLOAD
INPUT 8
CUSTOMER FURNISHED FAULT
INPUT 9
CUSTOMER FURNISHED WARNING
SOL1
LOAD CONTROL SOLENOID VALVE
SOL4
SEQUENCEING SOLENOID VALVE
SOL5
ELECTRIC CONDENSATE DRAIN VALVE
PS
24VDC POWER SUPPLY
K1
INTERNAL RUN RELAY CONTACT
K2
INTERNAL Y-DELTA START RELAY
K3
INTERNAL WYE-DELTA RUN RELAY
K4
INTERNAL LOAD CONTROL RELAY
K5
INTERNAL SEQUENCE RELAY
K6
INTERNAL ELECTRIC DRAIN RELAY
K7
INTERNAL COMMON FAULT RELAY
PF CAP
POWER FACTOR CORRECTION CAPACITOR (OPT'L)
HTR1
(OPT'L) SUMP HEATER 800W
HTR2
(OPT'L) HEAT TRACE
HTR3
(OPT'L) TRAP HEATER 70WATTS
HTR4
(OPT'L) CONTROL PANEL HEATER 50WATTS
TH
THERMOSTAT FOR HEAT TRACE OPTION
1FU
TRANSFORMER PRIMARY FUSES
2FU
TRANSFORMER SECONDARY FUSE 115V
3FU
TRANSFORMER SECONDARY FUSES 24V
4FU
FAN MOTOR BRANCH FUSES
Component Description
JZL
JZL DRAIN OPTION
XFMR
UNIVERSAL TRANSFORMER
1MCR
CONTROL RELAY FOR 300A CONTACTORS
Drawing notes
CUSTOMER TO FURNISH FUSED OR CIRCUIT BREAKER
1
DISCONNECT PER LOCAL CODES.
REMOVE JUMPER FOR AUXILIARY E-STOP STRING
2
DEVICES.
USE ISOLATING RELAYS WITH DRY CONTACTS FOR ANY
3
OPTIONAL INPUTS TO THE WS CONTROLLER™. MOUNT
THE RELAY LOCALLY IN THE STARTER BOX.